POLE ROZDZIELCZE

EH-d08-W/10/I/…

Ognioszczelne pole rozdzielcze

 

Specyfikacja techniczna

KEY FEATURES

2014/34/UE (ATEX)

double-break isolating switch

microprocessor-based instrument for measurement, automation, control and protection with power quality analyser

compact construction

Selected technical data

to 10 000 V

rated insulation voltage

to 10 000 V

rated switching voltage

to 12 000 V

maximum operating voltage

50/60 Hz

supply voltage frequency

to 630 A

rated continuous current

20 kA

rated short-circuit current

Technical
specifications

Characteristic features

Nagłowek całej skecji

Dwie kolumny

The flameproof distribution bay is an electrical switchgear for use in underground mining distribution networks with an isolated neutral point of the supply transformer. The switchgear is an explosion-proof device and, in accordance with Polish law, can be installed in underground workings of non-methane and methane mines with levels ‘a’ and ‘b’. The autonomous design predisposes the flameproof switchgear bay to be installed in single- to multi-section switchgear systems. The following switchgear bay designs are provided for the implementation of multi-field and sectioned switchgear: feeder, feeder-drain, outflow (including line, transformer and motor) and coupling.

The intended use and the division into flameproof compartments in the applied protection ensure safe cooperation in the switchgear system. The switchgear bay provides the function of controlling the continuity of earthing of the device located on the outlet, the control of cable shields and/or the outlet tyre conductor and methanometer systems. Switchboards with intrinsically safe circuits ensure remote control, correct cooperation with technological interlockings (including methanometric ones) and data transmission.

 

 

Technical data

DISTRIBUTION FIELD EH-d08-W/10/I/…

Rated insulation voltage 10 000 V
Rated switching voltage 10 000 V
Rated secondary voltage 12 000 V
Frequency 50, 60 Hz
Rated continuous current 630 A
Rated short-circuit current  20 kA
Rated peak residual current 50 kA
Short-circuit power of connected network  350 MVA
Exterior control circuits – spark-proof  ia
Degree of protection of the cover  IP54
Weight ~1600 kg

Configuration diagram

Schemat

DISTRIBUTION FIELD EH-d08-W/10/I/…

APPEARANCE, DIMENSIONS AND DESCRIPTION

Flameproof distribution box