Transformer station
FUTURA High Power Concrete by Elgór + Hansen is a comprehensive solution for reinforced concrete PV farms, combining modern technology, flexibility and trouble-free operation. Trust in modern solutions and gain efficiency and security for your energy infrastructure.
- High power – transformer up to 9MVA can be used.
- Intelligent management – remote control and monitoring.
- Modular, durable construction – easy to expand and customise to your needs.

Technical
specification
DESCRIPTION
The Futura High Power Concrete transformer station consists of a container part made of reinforced concrete, in which the MV and LV switchgears are located together with peripheral devices and a transformer part, where an MV/LV transformer with a maximum power of 9MVA is located behind the ventilation walls. Separating the station into a container part with MV and LV switchgears and an adjacent transformer part (technically coherent) increases the operational safety of the device. Placing the transformer outside the container part guarantees optimal working conditions for the electrical components inside the container. The ventilation walls of the transformer part ensure a continuous, undisturbed flow of air around the transformer, additionally enabling visual inspection of the device’s condition without having to switch off the station. Both parts of the station are set on a common reinforced concrete slab. The reinforced concrete slab effectively transfers loads to the ground, minimising the risk of subsidence and cracks.
BASIC TECHNICAL DATA
TRANSFORMER | |
Transformer rated power | 4500 – 9000 kVA |
Rated voltage | |
– SN | 15 kV; 20 kV; 30 kV |
– nn | 2×0,8 kV |
Rated frequency | 50 Hz |
Type of main transformer | oil |
Transformer cooling | ONAN |
Type of oil used | mineral oil |
Transformer connection group | Dyn5yn5 |
Tap changer / voltage regulation | ± 2 x 2.5% |
Peak Efficiency Index (PEI) | in accordance with the requirements of Eco Design Tier 2 |
Idle starts | in accordance with the requirements of Eco Design Tier 2 |
Chargeable losses | in accordance with the requirements of Eco Design Tier 2 |
MV SWITCHGEAR |
|
Rated voltage | 17,5 kV, 24 kV or 36 kV |
Continuous rated current | 630 A |
Short-term rated current (1 s) | 16 kA (1s) |
Peak rated current | 40 kA |
Resistance to internal arcing | 16 kA (1s) |
LV SWITCHGEAR | |
Main switches – amperage | up to 2 x 4000 A |
Rated switching current
Rated insulation voltage |
0,8 kV
1 kV |
In-line fuse-switch disconnectors | up to 20 400 A outputs per switchgear |
Auxiliary transformer | up to 75 kVA |
Configuration diagram
Are you looking for a modern power supply system?
We support our customers in every phase of their projects: from the planning stage, during construction, documentation and during operation, both at home and abroad.

Rafał Szołtysik
Commercial director
for electrical power engineering and industry